Submit manuscript...
MOJ
eISSN: 2577-8374

Solar and Photoenergy Systems

Correspondence:

Received: January 01, 1970 | Published: ,

Citation: DOI:

Download PDF

Abstract

This paper presents the adsorption and regeneration behavior of silica gel powder. For this, an experimental set-up has been purposed. The experimental set-up consists of silica gel coated heat exchanger, evacuated tube solar water heater and cooling tower. The evacuated tube solar water heater is used to generate hot water by using solar energy. This hot water is used to regenerate silica gel. The cooling tower is used to generate cooling water. This cooling water is used during adsorption process. Experimental results demonstrated that silica gel has a good adsorption capacity under northern Indian climatic condition and it can be easily regenerated by the help of solar energy. The adsorption capacity of the silica gel is significantly enhanced by using circulating water.

Keywords: evacuated tube solar water heater, silica gel coated heat exchanger, cooling tower

Introduction

The desiccant material is a material which has ability to remove moisture from air. According to the physical and chemical properties, there are two types of desiccant material namely solid desiccant material and liquid desiccant material. In this experimental study, solid desiccant material is used. Solid desiccant material adsorbs moisture from air due to water vapour pressure difference. Some common examples of solid desiccant material are silica gel, activated charcoal, molecular sieve and activated alumina. In recent years, numerous researchers have experimentally and theoretically investigated the adsorption and regeneration behavior various solar desiccant materials. Singh et al.1 experimentally investigated the regeneration behavior of silica gel by using multi self regenerator. The required regeneration temperature varied between 42°C to 72°C with a variation in velocity of 0.175 m/s to 0.55 m/s. Techajunta et al.2 experimentally and theoretically investigated adsorption and regeneration behavior of solid desiccant material for the application of air conditioning. Ge et al.3 experimentally compared silica gel and polymer coated fin-tube heat exchangers. It was found that the DCHE overcome the adsorption heat during desiccant dehumidification process and achieve good dehumidification performance under given conditions. The SCHE performed better as compared to the polymer coated heat exchanger. Ge et al.4 developed a mathematical model to predict the performance of SCHE cooling system under ARI summer condition and optimized the copper tube external diameter and distance between the fins. Ge et al.5 developed a mathematical model of a self-cooled solid desiccant cooling system by the combination of DCHE and regenerative evaporative cooler. The performance of the system was investigated under ARI summer condition and effect of outdoor air condition was analyzed. It was found that cooling power of the system increased by 30% as compared to DCHE cooling system. Yadav et al.6 experimentally investigated adsorption and regeneration behavior of different solid desiccant and found that silica gel was the best solid desiccant material among all solid desiccant material. Kumar et al.7 regenerated the silica gel by using parabolic dish and found that silica gel can be easily regenerated by using solar energy. Kumar et al.8 experimentally investigated an air conditioning system with various solid and composite desiccant material for the application of heating and humidification. It was found that silica gel is the most suitable desiccant material for particular application.

The main objectives of this experimental work are to investigate the regeneration and adsorption behavior of silica gel powder. The experimental setup has been fabricated and installed at NIT Kurukshetra, India [29° 58´ (latitude) North and 76°53´ (longitude) East].

Experimental Setup

Figure 1 shows the schematic diagram and photograph of the experimental setup. The main components of the experimental setup are:

    1. Evacuated tube solar water heater
    2. Silica gel coated heat exchanger (SCHE)
    3. Cooling tower

Figure 1 (a) Schematic diagram and (b) photograph of the experimental setup.

Evacuated tube solar water heater

It has 15 evacuated tubes and a header which is at an angle of 30° relative to horizontal surface with south facing. The evacuated tube has 2 coaxial tubes, namely glass and absorber tube. The length, outer diameters of the glass and absorber tube is 1500 mm, 47mm and 37 mm respectively. The header has a cross section of 100×140 mm2 with a length of 1160 mm respectively.

Silica gel coated heat exchanger

SCHE is constructed on the basic structure of shell and tube type heat exchanger with water capacity of 17.3 litres as shown in Figure 2. It has 64 aluminium tubes having a diameter of 25.4mm. The column chromatography silica gel is used as the coating desiccant material in this heat exchanger. Firstly, the silica gel particles are coated on the aluminium tubes of heat exchanger and then the aluminium tubes are dried and soaked in the silica gel solution repeatedly. The weight of silica gel coated on aluminium tubes is 1.7 kg.

Figure 2 Three-D view, schematic diagram and photographic view of the CDBHE.

Cooling tower

The cooling tower is used to produce cooling water for SCHE during the dehumidification process and also for heat exchanger in pre-cooling dehumidification. It has a cylindrical drum with a water capacity of 50 litres and a cellulose pad having a rectangular cross sectional area of 610×305 mm2 with a width of 51 mm. A water pump is used to circulate cooling water in SCHE and heat exchanger. The outlet water of the SCHE and heat exchanger is sprayed on the cellulose pad to regenerate the cooling water.

Working Principle of Experimental Setup

The system has been operated for, firstly regeneration process, then rest time and finally for adsorption process. During the regeneration process, the experimental setup was exposed to the Sun at 09:00 hr and reading was recorded from 10:00 hr to 15:00 hr. With the help of valves path-I was in working. The evacuated tube solar water heater produced the hot water and this hot water was transferred to the SCHE through connecting pipes due to thermosyphon phenomenon.

Then the regeneration air (ambient air) was pumped in the SCHE with the help of axial fan. The water vapours were transferred from the desiccant material to the regeneration air due to water vapour pressure difference. The desiccant material was completely regenerated at 15:00 hr then the hot water was drained out from the SCHE. A rest time period of half hour was maintained between the regeneration and adsorption process, so that the desiccant material could transfer its regeneration heat to the atmosphere. Now, the adsorption process was started at 15:30 hr. With the help of valves, the path-II was in working and the cooling water was circulated in the SCHE, which was generated by cooling tower. The adsorption heat produced by the desiccant material was taken by the cooling water. Then the process air (ambient air) was pumped in the SCHE with the help of axial fan. The water vapours were transferred from the process air to the desiccant material due to water vapour pressure difference. The dehumidification process was completed at 18:30 hr as the desiccant material was completely saturated.

Measuring Instruments and Uncertainty Analysis

Different parameters measured in these experiments are:

    1. Water temperature
    2. Air temperature and relative humidity
    3. Solar intensity
    4. Air flow rate

These parameters are measured by the following devices as given in Table 1. The uncertainty analysis used in this paper is based on the root mean square method as per Kline et al.9 The relationship for error analysis is given as

Δz= [ ( f y 1 ) 2 ( Δ y 1 ) 2 + ( f y 2 ) 2 ( Δ y 2 ) 2 +...+ ( f y n ) 2 ( Δ y n ) 2 ] 1 2 MathType@MTEF@5@5@+= feaagKart1ev2aaatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGWj0Jf9crFfpeea0xh9v8qiW7rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaqcLbsacqqHuo arcaWG6bGaeyypa0tddaWadaGcbaqddaqadaGcbaqddaWcaaGcbaqc LbsacqGHciITcaWGMbaakeaajugibiabgkGi2kaadMhanmaaBaaaje aqbaqcLbmacaaIXaaaleqaaaaaaOGaayjkaiaawMcaa0WaaWbaaSqa bKqaafaajugWaiaaikdaaaqddaqadaGcbaqcLbsacqqHuoarcaWG5b qddaWgaaqcbauaaKqzadGaaGymaaWcbeaaaOGaayjkaiaawMcaa0Wa aWbaaSqabKqaafaajugWaiaaikdaaaqcLbsacqGHRaWknmaabmaake aanmaalaaakeaajugibiabgkGi2kaadAgaaOqaaKqzGeGaeyOaIyRa amyEaKqbaoaaBaaajeaqbaqcLbmacaaIYaaajeaqbeaaaaaakiaawI cacaGLPaaanmaaCaaaleqajeaqbaqcLbmacaaIYaaaa0WaaeWaaOqa aKqzGeGaeuiLdqKaamyEa0WaaSbaaKqaafaajugWaiaaikdaaSqaba aakiaawIcacaGLPaaajuaGdaahaaqcbauabeaajugWaiaaikdaaaqc LbsacqGHRaWkcaGGUaGaaiOlaiaac6cacqGHRaWknmaabmaakeaanm aalaaakeaajugibiabgkGi2kaadAgaaOqaaKqzGeGaeyOaIyRaamyE a0WaaSbaaKqaafaajugWaiaad6gaaSqabaaaaaGccaGLOaGaayzkaa qddaahaaWcbeqcbauaaKqzadGaaGOmaaaanmaabmaakeaajugibiab fs5aejaadMhanmaaBaaajeaqbaqcLbmacaWGUbaaleqaaaGccaGLOa GaayzkaaqddaahaaWcbeqcbauaaKqzadGaaGOmaaaaaOGaay5waiaa w2faa0WaaWbaaSqabKqaafaajuaGdaWcaaqcbauaaKqzadGaaGymaa qcbauaaKqzadGaaGOmaaaaaaaaaa@8D1C@ …………………… (1)

Δz z = [ ( f y 1 ) 2 ( Δ y 1 z ) 2 + ( f y 2 ) 2 ( Δ y 2 z )+...+ ( f y n ) 2 ( Δ y n z ) 2 ] 1 2 MathType@MTEF@5@5@+= feaagKart1ev2aaatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGWj0Jf9crFfpeea0xh9v8qiW7rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaqddaWcaaGcba qcLbsacqqHuoarcaWG6baakeaajugibiaadQhaaaGaeyypa0tddaWa daGcbaqddaqadaGcbaqddaWcaaGcbaqcLbsacqGHciITcaWGMbaake aajugibiabgkGi2kaadMhanmaaBaaajeaqbaqcLbmacaaIXaaaleqa aaaaaOGaayjkaiaawMcaa0WaaWbaaSqabKqaafaajugWaiaaikdaaa qddaqadaGcbaqddaWcaaGcbaqcLbsacqqHuoarcaWG5bqddaWgaaqc bauaaKqzadGaaGymaaWcbeaaaOqaaKqzGeGaamOEaaaaaOGaayjkai aawMcaa0WaaWbaaSqabKqaafaajugWaiaaikdaaaqcLbsacqGHRaWk nmaabmaakeaanmaalaaakeaajugibiabgkGi2kaadAgaaOqaaKqzGe GaeyOaIyRaamyEa0WaaSbaaKqaafaajugWaiaaikdaaSqabaaaaaGc caGLOaGaayzkaaqddaahaaWcbeqcbauaaKqzadGaaGOmaaaanmaabm aakeaanmaalaaakeaajugibiabfs5aejaadMhanmaaBaaajeaqbaqc LbmacaaIYaaaleqaaaGcbaqcLbsacaWG6baaaaGccaGLOaGaayzkaa qcLbsacqGHRaWkcaGGUaGaaiOlaiaac6cacqGHRaWknmaabmaakeaa nmaalaaakeaajugibiabgkGi2kaadAgaaOqaaKqzGeGaeyOaIyRaam yEa0WaaSbaaKqaafaajugWaiaad6gaaSqabaaaaaGccaGLOaGaayzk aaqddaahaaWcbeqcbauaaKqzadGaaGOmaaaanmaabmaakeaanmaala aakeaajugibiabfs5aejaadMhanmaaBaaajeaqbaqcLbmacaWGUbaa leqaaaGcbaqcLbsacaWG6baaaaGccaGLOaGaayzkaaqddaahaaWcbe qcbauaaKqzadGaaGOmaaaaaOGaay5waiaaw2faa0WaaWbaaSqabKqa afaajuaGdaWcaaqcbauaaKqzadGaaGymaaqcbauaaKqzadGaaGOmaa aaaaaaaa@9074@ …………………….. (2)

Where f is a function of independent variable y1, y2, etc. stand for the variables of the function Δy1, Δy2 etc. are the absolute error associated with the variables and Δz z MathType@MTEF@5@5@+= feaagKart1ev2aaatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGWj0Jf9crFfpeea0xh9v8qiW7rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaqddaWcaaGcba qcLbsacqqHuoarcaWG6baakeaajugibiaadQhaaaaaaa@3CBA@ means the relative error. Based on these relationships, the test relative uncertainties for regeneration rate and adsorption rate are ± 5.3% and ± 16.5% respectively.

Sr. no.

Measurement

Sensors

Operational range

Accuracy

1

Water temperature

PT100 RTD

0°C to 200°C

± 0.3°C

2

Air Relative Humidity(RH)

and temperature

Hygrometer

0 to 100
-10°C to 60°C

± 2%

± 0.3°C

3

Air flow rate

Anemometer

0 to 45 m/s

± 2%

4

Solar intensity

Pyranometer

0 to 2000 W/m2

±2 W/m2

Table 1 measuring devices specifications

Performance Indices

Performances of the system are evaluated in terms of regeneration rate and adsorption rate.

Regeneration rate (đ‘…đ¶) can be given as

Regeneration rate (đ‘…đ¶) can be given as [2]

đ‘…đ¶ = 𝑚𝑎 (𝑌𝑜𝑱𝑡 - 𝑌𝑖𝑛)…………….. (3)

Adsorption rate (A𝑑) can be given as [2]

𝐮𝑑 = 𝑚𝑎 (𝑌𝑖𝑛 − 𝑌𝑜𝑱𝑡)…………… (4)

Where 𝑌𝑜𝑱𝑡 and 𝑌𝑖𝑛 is humidity ratio of process air at outlet and inlet condition of SCHE and is the mass flow rate of the process air.

Results and Discussion

For the system, the mass flow rate of process air and regeneration air are 0.046 kg/s. The hot water is naturally circulated in SCHE during the regeneration process. In adsorption process, the cooling water is circulated in the SCHE at the flow rate of 0.286 kg/s.

Regeneration process

The performance of desiccant material in regeneration process is greatly affected by circulated hot water temperature and the temperature of the hot water is affected by available solar intensity. So solar energy directly affects the regeneration rate of desiccant material.

Figure 3 represents the variations in water temperature of SCHE and solar intensity with time. It is observed from the graph that the water temperature of SCHE increases with solar intensity and attains its maximum value of 67.6°C and decreases slightly in last. After 13:00 hr the solar intensity decreases sharply and the water temperature of SCHE still increases, this is because of the sensible heat storage capacity of water.

Figure 3 Variation in water temperature of SCHE and solar intensity with time.

Figure 4 shows the variation in water temperature of SCHE and the regeneration rate of desiccant material with time. Initially, regeneration rate increases with increase in water temperature of SCHE, this is because, with an increase in surface temperature of desiccant material, the water vapour pressure difference between the desiccant material and the regeneration air increases. Hence the water vapour moves from desiccant material (high vapour pressure) to regeneration air (low vapour pressure). Then decrement in regeneration rate can be observed irrespective of increase in the water temperature. This shows that, the desiccant material is about to complete regeneration.

Figure 4 Variation in regeneration rate of the desiccant material and water temperature of SCHE with time.

Adsorption process

After complete regeneration of desiccant material, the dehumidification process has been started followed by a time gap. Figure 5 represents the variation in dehumidification rate and inlet air humidity ratio with time. In this case cooling water in not circulated in the SCHE. It is observed that the adsorption rate the desiccant material decreases continuously, which is the fundamental behavior of desiccant material. The average dehumidification rate of process air is 0.25 kg/h. The inlet air humidity ratio varies from 0.0205 kg water vapour/ kg dry air to 0.0218 kg water vapour/ kg dry air.

Figure 5 Variation in adsorption rate of desiccant material and inlet air humidity ratio with time in case of without circulating cooling water.

Figure 6 shows the variation in adsorption rate of the desiccant material with time. In this case, cooling water is circulated in the SCHE and desiccant material is regenerated at nearly similar condition as in last case. The adsorption rate of the desiccant material decreases continuously. This is because adsorption capacity of a desiccant bed decreases with time during the process. The average value of dehumidification rate is 0.49 kg/hr, which is higher than the last case. This is because of circulating cooling water. The cooling water removes adsorption heat from the desiccant material continuously. At lower surface temperature, the adsorption capacity of desiccant material significantly enhanced. The inlet air humidity ratio varies from 0.0207 kg water vapour/ kg dry air to 0.0218 kg water vapour/ kg dry air which is nearly similar to last case.

Figure 6 Variation in adsorption rate of desiccant material and inlet air humidity ratio with time in case of with circulating cooling water.

Conclusion

In this work, the regeneration and adsorption behavior of the silica gel powder is experimentally investigated. The following conclusions have been extracted from this experimental investigation (Table 2).

    1. The hot water temperature of the SCHE depends on the available solar intensity, whereas the regeneration rate of the desiccant material depends on the hot water temperature of the SCHE.
    2. The evacuated tube solar water heater produces hot water with an average temperature of 61.6°C, which is sufficient to regenerate the desiccant material of the system. So quite low regeneration temperature is required for the SCHE.
    3. The regeneration and adsorption rate of the desiccant material also depends upon the inlet air moisture content.
    4. The circulating cooling water is significantly enhanced the adsorption capacity of desiccant material.
    5. The amount of dry air produced by the SCHE is satisfactory, which can be used in air conditioning application.

Ad

Adsorption rate (kg/hr)

mass flow rate of process/regeneration air, kg/s

Rc

regeneration rate (kg/hr)

SCHE

silica gel coated heat exchanger

Yin

humidity ratio of process air at inlet of SCHE (kg/kg)

Yout

humidity ratio of process air at outlet of SCHE (kg/kg)

Table 2 Appendix

Acknowledgement

None.

Conflicts of interest

There is no conflict of interest.

References

  1. Singh S, Singh PP. Regeneration of silica gel in multi‒shelf regenerator. Renewable Energy. 1998;13(1):105‒119.
  2. Techajunta S, Chirarattananon S, Exell RHB. Experiments in a solar simulator on solid desiccant regeneration and air dehumidification for air conditioning in a tropical humid climate. Renewable Energy. 1999;17(4):549‒568.
  3. Ge TS, Dai YJ, Wang RZ, et al. Experimental comparison and analysis on silica gel and polymer coated fin‒tube heat exchangers. Energy. 2010;35(7):2893‒2900.
  4. Ge TS, Dai YJ, Wang RZ. Performance study of silica gel coated fin‒tube heat exchanger cooling system based on a developed mathematical model. Energy Conversion and Management. 2011;52(6):2329‒2338.
  5. Ge TS, Dai YJ, Li Y. Feasible study of a self‒cooled solid desiccant cooling system based on desiccant coated heat exchanger. Applied Thermal Engineering. 2013;58(1‒2):281‒290.
  6. Yadav A, Bajpai VK. Experimental comparison of various solid desiccants for regeneration by evacuated solar air collector and air dehumidification. Drying Technology. 2012;30(5):516‒525.
  7. Kumar A, Chaudhary A, Yadav A. The regeneration of various solid desiccants by using a parabolic dish collector and adsorption rate: An experimental investigation. International Journal of Green Energy. 2014;11(9):936‒953.
  8. Kumar A, Yadav A. Experimental investigation of solar heating and humidification system based on desiccant bed heat exchanger. International Journal of Ambient Energy. 2016;38(8):826‒833.
  9. Kline SJ, McClintock FA. Describing uncertainties in single‒sample experiments. Mech En. 1953;75:3‒8.
Creative Commons Attribution License

© . This is an open access article distributed under the terms of the, which permits unrestricted use, distribution, and build upon your work non-commercially.